Description
LO-SPCT-3000 Series split-core current transformer AC current from 400 to 3000 AMPS passing through the center conductor. Split core CTs are designed for fast and easy installation. The split core design permits non-contact current measurements through magnetic field induction without requiring that the primary wire be taken offline and disconnected for CT installation. This method permits a safer, easy and portable current measurement. An internal precision burden resistor across the secondary winding of the CT provides a safe low voltage output and permits safe opening of the secondary
Application
•Data logging•Recording•Power monitoring
•Energy management•Alternative energy monitoring
•Cost allocation
Features
Rated Current 400A to 3000A loads.
Rated output: 0.333VAC at rated current
Accuracy: ± 1% from 5% to 120% of rated current
Phase Angle: Less than 2 degrees at 50% of rated current
Maximum Primary Voltage: 5000VAC(Insulated Conductor)
Operating Temperature: -15C to 60C
Frequency Range: 50-400Hz
Leads: 4Feets(105cm), UL 1015, Twisted Pair, 0.34 mm2(22AWG)
CE recognized. RoHS Compliant
Output and leads can be customized
Model | I.D. | Rated Amps | Output | Accuracy | SIZE(mm) | ||||
A | B | C | D | E | |||||
LO-SPCT-0750 | 0.75" | 5, 15, 30, 50, 70, 100, 150, 200 | 0.333V | 1 | 51.6 | 54.1 | 16.6 | 19.1 | 18 |
(19.1mm) | |||||||||
LO-SPCT-1250 | 1.25" | 70, 100, 150, 200, 250, 300, 400, 600 | 1 | 82.3 | 85.3 | 26.4 | 32 | 32.3 | |
(31.8mm) | |||||||||
LO-SPCT-2000 | 2.00" | 400, 600, 800, 1000, 1200 | 1 | 120 | 125 | 29.6 | 52.5 | 52 | |
(50.8mm) | |||||||||
LO-SPCT-3000 | 3.00" x 5.00" | 1000, 1200, 1500,2000.3000 | 1 | 145 | 199 | 30.5 | 76 | 130 | |
(76.2mm x127mm) |