Description
Split core AC current sensors have different hole sizes and current ratings to suit any application. Split core models are perfect for retrofits. Output is fixed at the industry standard. It is easy to install, no need to dismantle the busbar, and can also be operated with electricity, without affecting the normal power consumption of the customer, saving manpower, material resources, financial resources and improving efficiency for the user transformation project.
Application
• Data logging • Recording • Power monitoring
• Energy management • Alternative energy monitoring
• Cost allocation
Features
• High accuracy at 10-150% of rated current
• AC isolation resistance: 3KV for 60s
• Swing open for ease of installation
• Phase angle <2 maximum at 50% rated current
• Rigid housing case with UL® 94V-0 durable plastic
• Safety standard: IEC/EN60044-1
• Nominal phase angle error and
Nominal linearity error: Conform IEC61869-2
ConformIEC60044-1
•Internal precision burden resistor across secondary.
Specification
Model | I.D. | Rated Amps | Output | Accuracy | SIZE(mm) | ||||
A | B | C | D | E | |||||
LO-SPCT-0750 | 0.75" | 5, 15, 30, 50, 70, 100, 150, 200 | 0.333V | 1 | 51.6 | 54.1 | 16.6 | 19.1 | 18 |
(19.1mm) | |||||||||
LO-SPCT-1250 | 1.25" | 70, 100, 150, 200, 250, 300, 400, 600 | 1 | 82.3 | 85.3 | 26.4 | 32 | 32.3 | |
(31.8mm) | |||||||||
LO-SPCT-2000 | 2.00" | 400, 600, 800, 1000, 1200 | 1 | 120 | 125 | 29.6 | 52.5 | 52 | |
(50.8mm) | |||||||||
LO-SPCT-3000 | 3.00" x 5.00" | 1000, 1200, 1500,2000.3000 | 1 | 145 | 199 | 30.5 | 76 | 130 | |
(76.2mm x127mm) |
About us
LIOU current transformers have been the industry leader in the design and production of current transformer products for more than 20 years. Our focus is on creating quality products designed to meet your needs. You can choose any of our standard products, or we can design and build custom solutions specifically for your application.