Electric Meter Mini CT-108 Micro Precision Current Transformer

Electric Meter Mini CT-108 Micro Precision Current Transformer

Description The LO-1001A3-L100 series of current sense transformers are designed to monitor AC currents. They can be used for high frequency current sensing, for example in switched-mode power supplies, motor control and electronic lighting ballasts. Features RoHS compliant 1000, 1500, 2000...
Chat Now

Product Details

With many years' effort, we have attained full experiences and abilities in developing our Ground Fault Residual Current, Hall Effect High Precision Current Sensor, High Precision Split Core Current Transducer according to customer's specifications. We continue to devote ourselves to innovation occupying the mid-to-high-end market with differentiated strategies, and strive to create a century-old brand. We warmly welcome merchants from home and abroad to call us and establish business relationship with us, and we will do our best to serve you. We fully respect the value of persons and pay attention to the exercise of the spirit of independence, creative potential and sense of responsibility of each employee as master. We got best suppliers support on quality and price.

Description

The LO-1001A3-L100 series of current sense transformers are designed to monitor AC currents. They can be used for

high frequency current sensing, for example in switched-mode power supplies, motor control and electronic lighting ballasts.


Features

RoHS compliant

1000, 1500, 2000 & 2500 Turn variants

Primary current up to 80A

50Hz-20kHz frequency range


Mechanical Specification

1

ELECTRIC SPECIFICATIONS @25C

SELECTION GUIDE

Order Code

Number of
Turns

Inductance
Min.

DC Resistance

Terminating Resistance

±5 Turn

Pins B&R

      Pins B&R, Ω                         

Ω

LO-1001A3-L100

2500

180H @0.5V, 50Hz

169.0MAX

100


ABSOLUTE MAXIMUM RATINGS

Operating free air temperature range

-40°C to 85°C

Storage temperature range

-40°C to 100°C


 LEADS INFORMATION

UL1015 20AWG BLACK & RED

Leads length:1010mm±10

Stripped and Tinned

10±3


Technical Notes

ISOLATION VOLTAGE

All LO-1001A3-L100 current sense transformers are tested at 2500VAC for a minimum of 3 seconds during our standard test procedure.

In addition, as part of our qualification process carried out prior to product launch, the 1001A3 series demonstrated no isolation breakdown at 10kVdc or 6kVac with a bare conductor as the primary winding. Whilst this does not imply these parts are designed for environments where such high voltages may be present, it does demonstrate the level of isolation voltage these products are able to withstand. Full mains safety isolation can be achieved with appropriately insulated wire on the primary winding.


How to Order?

1. Please let us know our P/N for off-the-shelf parts. Please send us electric specifications if you need custom-made parts.

2. Proforma invoice (PI) will be sent to you.

3. Please check and confirm the PI.

4. Once we confirmed the order, please pay it soon.

5. After full payment, all goods will be sent to you in 10-15 days as usual.

6. OEM/ODM is welcomed. Free OEM for more than 5000 sets orders.

QQ图片20200716135417_meitu_1

After years of development, with advanced R&D capabilities and professional operating capabilities, we have become a leading enterprise in the industry of Electric Meter Mini CT-108 Micro Precision Current Transformer and occupy an important position. Our company is based on technology, market-oriented, and service-oriented. Over the years, relying on the principles of diligence, pragmatism, integrity and thoughtful service, we have established a broad customer base and provided supply for many demand groups.

Inquiry

You Might Also Like